Friedrich EM18 User Manual

Room Air Conditioners  
Standard Chassis Models  
115-Volt: SS08, SS10, SS12, SS14  
230-Volt: SS12, SS16, SM18, SM21, SM24  
115-Volt: KS12, KS15  
230-Volt: KM18, KM24  
230-Volt: SL28, SL36  
HEAVY DUTY  
115-Volt: YS09  
230-Volt: YS13, YM18, YL24, ES12, ES16, EM18, EM24, EL36  
Register your air conditioner  
Model information can be found on the name  
plate behind the front cover.  
Please complete and mail the owner  
registration card furnished with this product,  
only). For your future convenience, record the  
model information here.  
MODEL NUMBER  
SERIAL NUMBER  
PURCHASE DATE  
920-198-00 (8-06)  
920-198-00  
WARNING: Before operating your unit  
Make sure the wiring is adequate for your unit.  
CIRCUIT RATING  
OR TIME DELAY  
FUSE  
REQUIRED WALL  
RECEPTACLE  
If you have fuses, they should be of the time delay type. Before you install  
or relocate this unit, be sure that the amperage rating of the circuit breaker  
or time delay fuse does not exceed the amp rating listed in Figure 1.  
MODEL  
NEMA  
NO.  
AMP  
VOLT  
DO NOT use an extension cord.  
The cord provided will carry the proper amount of electrical power to the  
unit; an extension cord will not.  
SS08 • SS10 • SS12 • SS14  
KS12 • KS15 • YS09  
15  
125  
5-15R  
6-15R  
6-20R  
SS12 • SS16 • SM18  
SM21 • KM18  
Make sure that the receptacle is compatible with  
the air conditioner cord plug provided.  
This insures proper grounding. If you have a two prong receptacle you  
will need to have it replaced with a grounded receptacle by a certied  
electrician. The grounded receptacle should meet all national and local  
codes and ordinances. Under no circumstances should you remove the  
ground prong from the plug. You must use the three prong plug furnished  
with the air conditioner.  
15  
20  
250  
250  
SM24 • SL28 • KM24  
YS13 • ES12 • ES16  
SL36 • YM18 • YL24  
EM18 • EM24 • EL36  
30  
250  
6-30R  
Figure 1  
Test the power cord  
All Friedrich room air conditioners are shipped from the factory with a  
Leakage Current Detection Interrupter (LCDI) equipped power cord. The  
LCDI device meets the UL and NEC requirements for cord connected air  
conditioners effective August 2004.  
NOTE: Your LCDI device will resemble one of these illustrations.  
To test your power supply cord:  
RESET  
TEST  
1. Plug power supply cord into a grounded 3 prong outlet.  
RESET  
2. Press RESET (See Figure 2).  
WARNING  
TEST BEFORE EACH USE  
1. PRESS RESET BUTTON  
TEST  
3. Press TEST (listen for click; Reset button trips and pops out).  
2. PLUG LDCI INTO POWER  
RECEPTACLE  
3. PRESS TEST BUTTON,  
RESET BUTTON SHOULD  
POP UP  
4. Press and release RESET (listen for click; Reset button latches and  
remains in). The power supply cord is ready for operation.  
4. PRESS TEST BUTTON,  
FOR USE  
DO NOT USE IF ABOVE TEST  
FAILS  
WHEN GREEN LIGHT IS ON  
IT IS WORKING PROPERLY  
NOTE: LCDI device is not intended to be used as a switch.  
Once plugged in the unit will operate normally without the need to reset  
the LCDI device.  
If the device fails to trip when tested or if the power supply cord is  
damaged it must be replaced with a new supply cord from the manufac-  
turer. We recommend you contact our Technical Assistance Line at  
(800) 541-6645 ext. 845. To expedite service, please have your model  
and serial number available.  
Figure 2  
For the best cooling performance and highest energy efficiency  
Keep the filter clean  
Make sure that your air conditioner is always in top performing condition  
by cleaning the filter regularly. Instructions for removing and cleaning the  
filter can be found on page 7.  
Insulation  
Good insulation will be a big help in maintaining desirable comfort levels.  
Doors should have weather stripping. Be sure to caulk around doors and  
windows.  
Provide good air flow  
Proper installation of seal gasket  
Make sure the airflow to and from the unit is clear. Your air conditioner puts the  
conditioned air out at the top of the unit, and takes in unconditioned air at the  
bottom. Airflow is critical to good operation. It is just as important on the outside  
of the building that the airflow around the unit exterior is not blocked.  
Make sure the seal gasket has been installed properly to minimize noise  
and improve efciency. If the seal gasket has not been installed, please  
refer to Step 14 (page 13) of the installation instructions.  
Also, if you switch from Cool mode to Fan Only, and switch back to  
COOL mode, there is a three minute delay before the compressor comes  
back on.  
Unit placement  
If your air conditioner can be placed in a window or wall that is shaded by a tree  
or another building, the unit will operate even more efficiently. Using drapes or  
blinds on the sunny side of the dwelling will also add to your unit’s efficiency.  
3
920-198-00  
How to operate your Friedrich room air conditioner (QuietMaster Programmable)  
To start unit  
1
If your air conditioner is installed and plugged into a proper re-  
ceptacle, it is ready to go. Touch Power button once. The unit will  
automatically be in Cool mode with the temperature set at 75°F  
(24°C) and the fan speed at F1, the sleep setting. There is a 3-  
minute delay before the compressor will turn on. (See "Automatic  
Component Protection" on this page).  
Should the Check Filter light turn on when you rst turn on the unit,  
touch Check Filter to turn off the light. Check Filter light will come  
on after 250 hours of use. (See page 7 for lter cleaning instructions.)  
Touch Check Filter to reset.  
Figure 3  
Set  
Hour  
Check  
Filter  
DISPLAY  
1
2
2
Press to reset  
12  
Power  
To set mode of operation  
4
5
3
When you rst turn on the unit, it will be in the Cool mode (light on),  
3
6
Money  
Saver  
Fan  
Only  
®
Cool  
with constant fan.  
Mode  
Temp  
Fan  
Touch MoneySaver® (light on) to activate the MoneySaver® feature.  
This cycles the fan with the compressor so that the fan does not  
run all the time. This saves energy and improves dehumidication.  
(MoneySaver® will also run the fan to sample the return air tempera-  
ture if the off cycle is too long). Or you may prefer constant fan for  
more air movement. To return to constant fan, touch Cool.  
4
OF/ OC  
8
7
9
11  
1-4  
Speed  
Smart  
Fan  
10  
14  
15  
5
Touch Fan Only (light on) if you want only the fan to run. You may want  
to use this feature in conjunction with the Fresh Air / Exhaust lever to  
bring outside air into a room, or to exhaust stale air. (See page 7, "Fresh  
Air and Exhaust Control" for more information.)  
13  
A/C  
Stop  
A/C  
Start  
Timer  
On/Off  
Timer  
To adjust temperature [60°F (16°C) to 90°F (32°C)]  
6
7
8
COOLER – Touch and hold until the display shows the desired  
room temperature.  
WARMER – Touch  
and hold until the display shows the desired  
To set the timer  
NOTE: Set Hour clock before attempting to set timer functions.  
room temperature.  
FAHRENHEIT / CELSIUS Touch ºF/ºCto show the temperature  
in Celsius, touch again to show Fahrenheit.  
You can set the A/C Start and A/C Stop timer a minimum of one hour  
apart and a maximum of 23 hours apart.  
To adjust fan speed  
TIMER STOP - Press the A/C Stop button and continue pressing  
until the hour you want the unit to shut off appears in the display  
(A.M. or P.M.). The stop time for cooling will then be set.  
13  
9
Touch 1-4 Speed to see current setting. Touch again to change  
speed. F1 is the lowest setting (SLEEP SETTING), F2 is low speed  
(LOW), F3 is medium speed (MED), F4 is high speed (HIGH).  
START TIME - Press A/C Start to view the current start time for  
cooling. Continue pressing until the hour you want the unit to start  
appears in the display (A.M. or P.M.). The start time for cooling will  
then be set.  
14  
To activate smart fan  
Touch Smart Fan (light on). Smart Fan will adjust the fan speed  
automatically to maintain the desired comfort level. For example,  
if the outside doors in your home are open for an extended period  
of time, or more people enter a room, Smart Fan may adjust to a  
higher fan speed to compensate for the increased heat load. This  
keeps you from having to adjust the fan speed on your own. Smart  
Fan cannot be activated in the Fan Only mode.  
10  
Press the Timer On/ Off button once to activate (light on) the timer  
function. Touch Timer On/ Off again (light off) to cancel the timer  
function if you so desire. Once the on and off times have been se-  
lected, they will remain in memory, and cycle daily until changed.  
15  
NOTE: If unit is unplugged or power is interrupted, the Set Hour button  
must be reset or the Timer On/ Off functions will not work.  
To deactivate smart fan  
Touch 1-4 Speed, and select your desired fan speed.  
11  
Automatic component protection  
Your unit is equipped with Automatic Component Protection.  
To set hour clock  
Press Set Hour once to see the current clock setting. Continue  
12  
pressing the button until the hour closest to the actual time appears  
in the display.  
To protect the compressor of the unit, there is a three minute time delay if you  
turn the unit off or if power is interrupted. The fan will not be affected.  
MAKE SURE YOU SET A.M. AND P.M. PROPERLY. A light will appear in  
the upper left corner of the display when the hour is P.M.  
NOTE: Minutes will NOT show on display.  
4
920-198-00  
*
How to use the remote control (QuietMaster Programmable)  
To start unit  
To set the timer  
1
POWER - Press the Power button once. The unit will automatically  
turn on in the mode and fan speed it was last left on.  
NOTE: Set the hour clock before attempting to set timer functions. You  
can set the timer On/Off a minimum of one hour apart, and a maximum  
of 23 hours apart.  
To set mode of operation  
2
9
TIMER START - Press Start to view the current start time for cool-  
ing. Continue pressing the Start button until you arrive at the start  
time you desire. The start time for cooling will then be set.  
COOL - Press the Cool button to automatically switch the operating  
mode to COOL.  
TIMER STOP - Press the Stop button. Continue pressing the Stop  
button until you arrive at the stop time you desire. The stop time for  
cooling will then be set.  
10  
11  
3
FAN ONLY - Press the Fan Only button if you want to run the fan only.  
You may want to use this feature in conjunction with the Fresh Air/  
Exhaust if you want to bring outside air into the room, or exhaust stale  
air. (The FRESH AIR / EXHAUST feature is located on the front of the  
air conditioner near the top. See Figure 9 on page 7.)  
TIMER ON/OFF - Press the On/off button once to activate (light on)  
or deactivate (light off) the timer. Once the Start and Stop times  
have been selected, they will remain in memory, and cycle daily until  
changed.  
4
MoneySaver® - Press the MoneySaver® button to activate the  
MoneySaver® feature. This cycles the fan with the compressor so  
that the fan does not run all the time.  
NOTE: If the unit is unplugged or the power is interrupted, the HOUR  
CLOCK must be reset or the Timer On/off functions will not work.  
To adjust temperature  
5
COOLER - Press the  
Cooler button to raise the temperature  
setting.  
Figure 4  
6
WARMER - Press the  
Warmer button to lower the temperature  
setting.  
To adjust fan speed  
7
FAN SPEED - Press the Fan Speed button to see the current set-  
ting. Press again to change the fan speed. F1 is the lowest setting  
(SLEEP SETTING), F2 is low speed (LOW), F3 is medium (MED),  
and F4 is high (HIGH).  
Temperature  
Cooler  
Warmer  
Power  
6
5
Cool  
2
3
1
4
7
8
To set the hour clock  
Fan  
Fan  
Money  
Saver®  
8
SET HOUR CLOCK - Press Set Hour once to see the current clock set-  
Only  
Speed  
ting. Continue pressing the button until you arrive at the current time.  
Timer Operation  
On/Off Start Stop Set Hr.  
11  
9
MAKE SURE YOU SET THE A.M. AND P.M. PROPERLY. (NOTE:  
MINUTES ARE NOT SHOWN ON THE DISPLAY.) A light will appear in  
the upper left corner of the display when the hour is P.M.  
10  
*
A Friedrich RC1 wireless remote control can be used to operate all  
QuietMaster® Programmable models.  
5