Room Air Conditioners
Standard Chassis Models
115-Volt: SS08, SS10, SS12, SS14
230-Volt: SS12, SS16, SM18, SM21, SM24
115-Volt: KS12, KS15
230-Volt: KM18, KM24
230-Volt: SL28, SL36
HEAVY DUTY
115-Volt: YS09
230-Volt: YS13, YM18, YL24, ES12, ES16, EM18, EM24, EL36
Register your air conditioner
Model information can be found on the name
plate behind the front cover.
Please complete and mail the owner
registration card furnished with this product,
only). For your future convenience, record the
model information here.
MODEL NUMBER
SERIAL NUMBER
PURCHASE DATE
920-198-00 (8-06)
920-198-00
WARNING: Before operating your unit
Make sure the wiring is adequate for your unit.
CIRCUIT RATING
OR TIME DELAY
FUSE
REQUIRED WALL
RECEPTACLE
If you have fuses, they should be of the time delay type. Before you install
or relocate this unit, be sure that the amperage rating of the circuit breaker
or time delay fuse does not exceed the amp rating listed in Figure 1.
MODEL
NEMA
NO.
AMP
VOLT
DO NOT use an extension cord.
The cord provided will carry the proper amount of electrical power to the
unit; an extension cord will not.
SS08 • SS10 • SS12 • SS14
KS12 • KS15 • YS09
15
125
5-15R
6-15R
6-20R
SS12 • SS16 • SM18
SM21 • KM18
Make sure that the receptacle is compatible with
the air conditioner cord plug provided.
This insures proper grounding. If you have a two prong receptacle you
will need to have it replaced with a grounded receptacle by a certified
electrician. The grounded receptacle should meet all national and local
codes and ordinances. Under no circumstances should you remove the
ground prong from the plug. You must use the three prong plug furnished
with the air conditioner.
15
20
250
250
SM24 • SL28 • KM24
YS13 • ES12 • ES16
SL36 • YM18 • YL24
EM18 • EM24 • EL36
30
250
6-30R
Figure 1
Test the power cord
All Friedrich room air conditioners are shipped from the factory with a
Leakage Current Detection Interrupter (LCDI) equipped power cord. The
LCDI device meets the UL and NEC requirements for cord connected air
conditioners effective August 2004.
NOTE: Your LCDI device will resemble one of these illustrations.
To test your power supply cord:
RESET
TEST
1. Plug power supply cord into a grounded 3 prong outlet.
RESET
2. Press RESET (See Figure 2).
WARNING
TEST BEFORE EACH USE
1. PRESS RESET BUTTON
TEST
3. Press TEST (listen for click; Reset button trips and pops out).
2. PLUG LDCI INTO POWER
RECEPTACLE
3. PRESS TEST BUTTON,
RESET BUTTON SHOULD
POP UP
4. Press and release RESET (listen for click; Reset button latches and
remains in). The power supply cord is ready for operation.
4. PRESS TEST BUTTON,
FOR USE
DO NOT USE IF ABOVE TEST
FAILS
WHEN GREEN LIGHT IS ON
IT IS WORKING PROPERLY
NOTE: LCDI device is not intended to be used as a switch.
Once plugged in the unit will operate normally without the need to reset
the LCDI device.
If the device fails to trip when tested or if the power supply cord is
damaged it must be replaced with a new supply cord from the manufac-
turer. We recommend you contact our Technical Assistance Line at
(800) 541-6645 ext. 845. To expedite service, please have your model
and serial number available.
Figure 2
For the best cooling performance and highest energy efficiency
Keep the filter clean
Make sure that your air conditioner is always in top performing condition
by cleaning the filter regularly. Instructions for removing and cleaning the
filter can be found on page 7.
Insulation
Good insulation will be a big help in maintaining desirable comfort levels.
Doors should have weather stripping. Be sure to caulk around doors and
windows.
Provide good air flow
Proper installation of seal gasket
Make sure the airflow to and from the unit is clear. Your air conditioner puts the
conditioned air out at the top of the unit, and takes in unconditioned air at the
bottom. Airflow is critical to good operation. It is just as important on the outside
of the building that the airflow around the unit exterior is not blocked.
Make sure the seal gasket has been installed properly to minimize noise
and improve efficiency. If the seal gasket has not been installed, please
refer to Step 14 (page 13) of the installation instructions.
Also, if you switch from Cool mode to Fan Only, and switch back to
COOL mode, there is a three minute delay before the compressor comes
back on.
Unit placement
If your air conditioner can be placed in a window or wall that is shaded by a tree
or another building, the unit will operate even more efficiently. Using drapes or
blinds on the sunny side of the dwelling will also add to your unit’s efficiency.
3
920-198-00
How to operate your Friedrich room air conditioner (QuietMaster Programmable)
To start unit
1
If your air conditioner is installed and plugged into a proper re-
ceptacle, it is ready to go. Touch Power button once. The unit will
automatically be in Cool mode with the temperature set at 75°F
(24°C) and the fan speed at F1, the sleep setting. There is a 3-
minute delay before the compressor will turn on. (See "Automatic
Component Protection" on this page).
Should the Check Filter light turn on when you first turn on the unit,
touch Check Filter to turn off the light. Check Filter light will come
on after 250 hours of use. (See page 7 for filter cleaning instructions.)
Touch Check Filter to reset.
Figure 3
Set
Hour
Check
Filter
DISPLAY
1
2
2
Press to reset
12
Power
To set mode of operation
4
5
3
When you first turn on the unit, it will be in the Cool mode (light on),
3
6
Money
Saver
Fan
Only
®
Cool
with constant fan.
Mode
Temp
Fan
Touch MoneySaver® (light on) to activate the MoneySaver® feature.
This cycles the fan with the compressor so that the fan does not
run all the time. This saves energy and improves dehumidification.
(MoneySaver® will also run the fan to sample the return air tempera-
ture if the off cycle is too long). Or you may prefer constant fan for
more air movement. To return to constant fan, touch Cool.
4
OF/ OC
8
7
9
11
1-4
Speed
Smart
Fan
10
14
15
5
Touch Fan Only (light on) if you want only the fan to run. You may want
to use this feature in conjunction with the Fresh Air / Exhaust lever to
bring outside air into a room, or to exhaust stale air. (See page 7, "Fresh
Air and Exhaust Control" for more information.)
13
A/C
Stop
A/C
Start
Timer
On/Off
Timer
To adjust temperature [60°F (16°C) to 90°F (32°C)]
6
7
8
COOLER – Touch and hold until the display shows the desired
room temperature.
WARMER – Touch
and hold until the display shows the desired
To set the timer
NOTE: Set Hour clock before attempting to set timer functions.
room temperature.
FAHRENHEIT / CELSIUS –Touch ºF/ºCto show the temperature
in Celsius, touch again to show Fahrenheit.
You can set the A/C Start and A/C Stop timer a minimum of one hour
apart and a maximum of 23 hours apart.
To adjust fan speed
TIMER STOP - Press the A/C Stop button and continue pressing
until the hour you want the unit to shut off appears in the display
(A.M. or P.M.). The stop time for cooling will then be set.
13
9
Touch 1-4 Speed to see current setting. Touch again to change
speed. F1 is the lowest setting (SLEEP SETTING), F2 is low speed
(LOW), F3 is medium speed (MED), F4 is high speed (HIGH).
START TIME - Press A/C Start to view the current start time for
cooling. Continue pressing until the hour you want the unit to start
appears in the display (A.M. or P.M.). The start time for cooling will
then be set.
14
To activate smart fan
Touch Smart Fan (light on). Smart Fan will adjust the fan speed
automatically to maintain the desired comfort level. For example,
if the outside doors in your home are open for an extended period
of time, or more people enter a room, Smart Fan may adjust to a
higher fan speed to compensate for the increased heat load. This
keeps you from having to adjust the fan speed on your own. Smart
Fan cannot be activated in the Fan Only mode.
10
Press the Timer On/ Off button once to activate (light on) the timer
function. Touch Timer On/ Off again (light off) to cancel the timer
function if you so desire. Once the on and off times have been se-
lected, they will remain in memory, and cycle daily until changed.
15
NOTE: If unit is unplugged or power is interrupted, the Set Hour button
must be reset or the Timer On/ Off functions will not work.
To deactivate smart fan
Touch 1-4 Speed, and select your desired fan speed.
11
Automatic component protection
Your unit is equipped with Automatic Component Protection.
To set hour clock
Press Set Hour once to see the current clock setting. Continue
12
pressing the button until the hour closest to the actual time appears
in the display.
To protect the compressor of the unit, there is a three minute time delay if you
turn the unit off or if power is interrupted. The fan will not be affected.
MAKE SURE YOU SET A.M. AND P.M. PROPERLY. A light will appear in
the upper left corner of the display when the hour is P.M.
NOTE: Minutes will NOT show on display.
4
920-198-00
*
How to use the remote control (QuietMaster Programmable)
To start unit
To set the timer
1
POWER - Press the Power button once. The unit will automatically
turn on in the mode and fan speed it was last left on.
NOTE: Set the hour clock before attempting to set timer functions. You
can set the timer On/Off a minimum of one hour apart, and a maximum
of 23 hours apart.
To set mode of operation
2
9
TIMER START - Press Start to view the current start time for cool-
ing. Continue pressing the Start button until you arrive at the start
time you desire. The start time for cooling will then be set.
COOL - Press the Cool button to automatically switch the operating
mode to COOL.
TIMER STOP - Press the Stop button. Continue pressing the Stop
button until you arrive at the stop time you desire. The stop time for
cooling will then be set.
10
11
3
FAN ONLY - Press the Fan Only button if you want to run the fan only.
You may want to use this feature in conjunction with the Fresh Air/
Exhaust if you want to bring outside air into the room, or exhaust stale
air. (The FRESH AIR / EXHAUST feature is located on the front of the
air conditioner near the top. See Figure 9 on page 7.)
TIMER ON/OFF - Press the On/off button once to activate (light on)
or deactivate (light off) the timer. Once the Start and Stop times
have been selected, they will remain in memory, and cycle daily until
changed.
4
MoneySaver® - Press the MoneySaver® button to activate the
MoneySaver® feature. This cycles the fan with the compressor so
that the fan does not run all the time.
NOTE: If the unit is unplugged or the power is interrupted, the HOUR
CLOCK must be reset or the Timer On/off functions will not work.
To adjust temperature
5
COOLER - Press the
Cooler button to raise the temperature
setting.
Figure 4
6
WARMER - Press the
Warmer button to lower the temperature
setting.
To adjust fan speed
7
FAN SPEED - Press the Fan Speed button to see the current set-
ting. Press again to change the fan speed. F1 is the lowest setting
(SLEEP SETTING), F2 is low speed (LOW), F3 is medium (MED),
and F4 is high (HIGH).
Temperature
Cooler
Warmer
Power
6
5
Cool
2
3
1
4
7
8
To set the hour clock
Fan
Fan
Money
Saver®
8
SET HOUR CLOCK - Press Set Hour once to see the current clock set-
Only
Speed
ting. Continue pressing the button until you arrive at the current time.
Timer Operation
On/Off Start Stop Set Hr.
11
9
MAKE SURE YOU SET THE A.M. AND P.M. PROPERLY. (NOTE:
MINUTES ARE NOT SHOWN ON THE DISPLAY.) A light will appear in
the upper left corner of the display when the hour is P.M.
10
*
A Friedrich RC1 wireless remote control can be used to operate all
QuietMaster® Programmable models.
5
|